From: James Priest [priest@fnal.gov] Sent: Friday, June 19, 2009 11:17 AM To: Linda Bagby Subject: MINERVA Cable Tests The CAT6E Belden 7852A and the twpr Belden 9409 passed the tests for use underground will not propagate flame had the lowest smoke density and off gas of HCL/HBR. I provided you with DVD's of the tests for your records and the failed cable tests of the other samples. On Aug 5, 2009, at 10:56 AM, Linda Bagby wrote: Hi, We need to install some cable tray on a relay rack in the MINOS hall for Minerva. We have purchased G type raceway from Panduit which is made from Lead-free PVC and has rating of UL94 Flammability rating of V-0. According to a BAPI web link V-0 Vertical Burn characteristics state that No flaming drips are allowed for this rating. Is this material adequate for installation in the MINOS hall? Does it have to be tested? Thanks, Linda On Aug 5, 2009, at 4:48 PM, Linda Bagby wrote: Hi, I left a section of the material and spec sheets on your desk. Here’s the BAPI note I was citing. http://www.bapihvac.com/CatalogPDFs/I_App_Notes/UL94_Rating.pdf Here’s the type of tray we plan to install. http://www.alliedelec.com/Images/Products/Datasheets/BM/PANDUIT/381- 0596.PDF From: James Priest [priest@fnal.gov] Sent: Sunday, August 09, 2009 8:07 PM To: Linda Bagby Subject: Re: cable raceway for Minerva You can use it. If you have a fire that hot you have other issues. The pH comes from the Bromine halogen HBR they use for the fire retarant properties. A non halogen plastic would be great but hard to find on this side of the pond.